POWER ONE CENTRALIZED
Listed below are the requirements for initial action on a failed inverter. Before proceeding with any operation: A) Verify that the model is correct; B) Carefully follow all instructions provided in the manufacturer’s operation and maintenance manual; C) Ensure that the intervention is carried out by trained personnel; D) Since this is a photovoltaic inverter with a DC input that is always live, strictly observe all applicable safety regulations.
Alarms, Errors and Warnings
Messaggio di allarme |
Allarme |
Codice a display |
Possibile causa |
Possibile soluzione |
---|---|---|---|---|
|
Display off |
/ |
(a) If the problem is common to all modules in the rack: No auxiliary voltage |
(a) Check the status and voltage at the terminals of the Aux disconnect switch inside the ACbox. Rebend the auxiliary voltage distribution harnesses, starting from the bottom to the top. |
Energy Save |
/ |
/ |
(a) Insufficient DC voltage |
a) - Open the left front panel and check for DC voltage (at least 350V). |
Waiting sun-net |
/ |
/ |
(a) (if the problem is common to all modules): No voltage on AC side |
(a) Check the voltage at the terminals of the AC switch. |
Iin high |
Input current above the maximum threshold |
E001 |
(a) Incorrect sizing of the PV generator. Error in plant implementation. |
(a) Check whether the composition of the PV generator is within the DC limits of the inverter. It is possible that this state leads to a halt in the conversion process due to DC fuse tripping. Adjust the system to the limits of the inverter. |
Bulk OV |
Input voltage above the maximum threshold |
E004 |
(a) Incorrect sizing of the PV generator. Error in plant implementation. |
(a) Check the DC voltage input to the inverter. |
Error com. |
Communication error with the DSP |
E005 |
(a) Internal module failure |
(a) Perform a complete restart cycle of the inverter. |
Overcorr |
Output current outside the maximum threshold |
E006 |
(a) Short circuit on the AC side of the inverter. AC line voltage failure. |
(a) Dissect the module completely: |
OCH |
IGBT SAT |
E007 |
(a) Disturbance/grid hole/low irradiance (morning, evening). |
In case of occasional error or alternating on various forms: |
Overtemp. |
Overtemperature |
E014 |
(a) Temperature probe failure, ambient temperature above 60°, filters blocked. |
(a) Through the Aurora CVI Central software verify: |
Bulk sbil. |
Voltage difference on DC capacitors above |
E015 |
(a) Insulation loss of the PV generator. |
(a) Dissect the module completely: |
Low temp. |
Temperature below the minimum threshold |
E033 |
(a) Ambient temperature below -10°. |
a) Through the Aurora CVI Central software, in the INVERTER MONITORING menu, check whether the default value of the thresholds MCU°C, P. Feed |
Remote off |
Remote off |
E035 |
(a) Remote off by software command. |
a) Through the Aurora CVI Central softaware reset Remote ON from the MODULE-> COMMANDS->SOFTWARE COMMANDS-> REMOTE ON/OFF SETTINGS menu. |
Iin low |
Negative input current above the maximum threshold |
E037 |
(a) Negative DC input current |
a) Through the Aurora CVI Central Software download the fault log and check the recurrence of the error. |
Knockout fans |
Blocked fans |
E038 |
(a) Presence of foreign bodies. |
(a) Check the condition of the filters and inspect the front panel at the central fan. If the error is permanent, contact Service STI Repair. |
DC open |
DC disconnector open |
E039 |
(a) DC disconnector open. |
(a) Check the status of the DC disconnect switch by removing the left front panel. |
AC open |
AC disconnector open |
E040 |
(a) AC switch open/fault at auxiliary contact, dipswitch board fault. |
(a) If the error is present on all modules in the same rack, check the status of the switch and auxiliary contact present inside the AC disconnector. |
Interr. AC |
The internal AC contactor has not switched |
E041 |
(a) Failure of the contactor inside the module. |
Perform a complete restart cycle of the inverter. |
Low Bulk |
Capacitor voltage below the minimum threshold |
E042 |
(a) DC-side voltage below the minimum threshold |
a) Through the Aurora CVI Central Software download the fault log, check the recurrence of the error. If the error is permanent, try swapping the module with another one from the same rack. If the error persists in the same form contact Service STI Repair. |
Auto Excl. |
Self-exclusion of the module due to repeated failures |
E043 |
(a) The module detected a high number of errors of the same type. |
(a) The module is in the state of self-exclusion from the system to avoid further damage. The errors that can bring the module to this state are: E005, E007, E015, E038. It is necessary to use Aurora CVI Central Software to unlock the module and download the fault log to understand the initial cause that generated the self-exclusion state. In case of E038, the module will self-exclude 900 seconds after the first error is detected. |
A.I. Warn |
/ |
/ |
(a) Lack of anti-island pulse on jbox serial. |
(a) This status does not affect the output of the inverter in any way and indicates that no module has been set up as stringcomb manager via the Aurora CVI Central Software. In case you are not using FIMER stringcombs, it is possible to set a module as stringcomb manager by setting in number of stringcombs equal to zero (CONFIGURATION PLANT-> STRINGCOMB MANAGER-> SET). |
OV network |
OV Line voltage |
W004 |
(a) AC voltage too high, high grid impedance, unsuitable AC cable cross section, incorrect AC cable wiring. |
a) Fully section the module by opening the AC switch on board inverter, the DC disconnector and the Auxiliary power supply. Through the use of a tester, verify the origin of the fault. |
UV net |
UV Mains voltage |
W005 |
(a) AC voltage too low, incorrect AC cable wiring. |
a) Fully section the module by opening the AC switch on board inverter, the DC disconnector and the Auxiliary power supply. Through the use of a tester, verify the origin of the fault. |
OF network |
OF network |
W006 |
(a) Grid frequency above the maximum threshold, grid transient, AC breaker trip or inverter edge contactor. |
a) Fully section the module by opening the AC switch on board inverter, the DC disconnector and the Auxiliary power supply. Check the origin of the anomaly. |
UF network |
UF network |
W007 |
(a) Grid frequency below the minimum threshold, grid transient, AC breaker tripping or inverter edge contactor. |
a) Fully section the module by opening the AC switch on board inverter, the DC disconnector and the Auxiliary power supply. Check the origin of the anomaly. |
Pot. nothing |
Zero exported power |
W014 |
(a) Zero exported power |
a) Through the Aurora CVI Central Software download the fault log, check the recurrence of the error. If the error is permanent, try swapping the module with another one from the same rack. If the error persists in the same form contact Service STI Repair. |
Df/dt network |
Df/dt network |
W015 |
(a) Conditions of transient island operation. |
a) Fully section the module by opening the AC switch on board inverter, the DC disconnector and the Auxiliary power supply. Check the origin of the anomaly. |
|
Surge Protector Device |
W016 |
(a) DC-side cartridge varistor trip, failure of auxiliary status contact. |
(a) Remove the left front panel and check: |
Jbox Err. |
One or more StringCombs have communicated a problem |
W017 |
(a) Generic stringcomb error |
(a) Check using Aurora CVI Central Software for the recurrence of the warning (STRINGCOMB MONITORING). |
Quartz failure |
Desynchronization of the two MCU-managed clocks |
/ |
(a) Short quartz |
(a) The inverter does not give functional problems, there may be problems in recording statistics. Contact Service STI Repair. |
Low Battery |
Desynchronization of the two MCU-managed clocks |
/ |
(a) Live battery |
(a) The inverter does not give functional problems, there may be problems in recording statistics. Contact Service STI Repair. |